| Kipengele | Thamani |
|---|---|
| 5 V DC ... 30 V DC (200 mA DC) | |
| Dokezo | 2018 |
| Aina | DIN rail module, one-piece |
| Kina | 65.5 mm (incl. DIN rail 7.5 mm) |
| Upana | 71.2 mm |
| Urefu | ≤ 6000 m (amsl) |
| Aina ya EN | T2 |
| Aina ya bidhaa | Surge arrester |
| Uzi wa skrubu | M5 |
| Aina ya kupachika | DIN rail: 35 mm |
| Jina la muunganisho | Remote fault indicator contact |
| Mlalo wa sauti | 4 Div. |
| Nyenzo za makazi | PA 6.6 |
| Kiwango cha uchafuzi wa mazingira | 2 |
| Muda wa majibu tA | ≤ 25 ns |
| Urefu wa kukatwa | 16 mm |
| Mbinu ya muunganisho | Screw connection |
| AWG ya sehemu mtambuka | (converted acc. to IEC) |
| Mkondo wa uendeshaji | 5 mA AC ... 1.5 A AC |
| Volti ya uendeshaji | 5 V AC ... 250 V AC (Altitude ≤ 2000 m amsl) |
| Mshtuko (upasuaji) | 50g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Kukaza torque | 3 Nm |
| Njia ya ulinzi | (DC+) - (DC-) |
| Volti ya kawaida ya Umoja wa Mataifa | 750 V DC |
| Kitendakazi cha kubadilisha | Changeover contact |
| Mchoro wa vipimo | |
| Mwelekeo wa kitendo | (L+)-PE & (L-)-PE & (L+)-(L-) |
| Nyenzo za kuhami joto | PA 6.6 |
| Kiwango cha ulinzi | IP20 (only when all terminal points are used) |
| Kategoria ya volteji nyingi | III |
| IPE ya mkondo uliobaki | ≤ 70 µA DC |
| Thamani ya nyenzo ya CTI | 600 |
| Imekadiriwa IL ya sasa ya mzigo | 40 A |
| Ure za volteji zilizobaki | ≤ 3.3 kV (at In) |
| Mtetemo (uendeshaji) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
| Mfumo wa usambazaji wa umeme wa IEC | DC |
| Uainishaji wa mtihani wa IEC | T2 |
| Viwango/vipimo | IEC 61643-31 |
| Sehemu ya msalaba ya kondakta AWG | 14 ... 2 |
| Kiwango cha ulinzi wa volteji kimepanda | ≤ 3.3 kV |
| Kompyuta ya matumizi ya nguvu ya kusubiri | ≤ 70 mVA |
| Sehemu ngumu ya kondakta | 0.14 mm² ... 1.5 mm² |
| Kiwango cha juu cha voltage inayoendelea UC | 800 V DC |
| Ujumbe wa hitilafu ya ulinzi dhidi ya kuongezeka kwa kasi | Optical, remote indicator contact |
| Halijoto ya mazingira (uendeshaji) | -40 °C ... 80 °C |
| Sehemu ya msalaba ya kondakta inayonyumbulika | 2.5 mm² ... 35 mm² |
| Unyevu unaoruhusiwa (uendeshaji) | 5 % ... 95 % |
| Ukadiriaji wa mkondo wa mzunguko mfupi ISCCR | min. 1 kA DC (with maximum backup fuse 40 A gG/1200 V DC) |
| Fuse ya chelezo ya kiwango cha juu zaidi yenye waya wa tawi | 40 A (gG / 1200 V DC) |
| Ukadiriaji wa kuwaka kulingana na UL 94 | V-0 |
| Mkondo wa kutokwa kwa nominella Katika (8/20) µs | 20 kA |
| Halijoto ya kawaida (uhifadhi/usafiri) | -40 °C ... 80 °C |
| Kiwango cha juu cha mkondo wa kutokwa (8/20) µs | 40 kA |
| Jumla ya mkondo wa kutokwa Jumla (8/20) µs | 40 kA |
Speci za kiufundi na data ya utendaji
Mwongozo wa usakinishaji na uendeshaji